Installing A Honeywell Humidifier

Like I have stated in past posts its not always easy in this part of the country to add a humidifier, here I have a customer that is required by his doctor to bring up their humidity in their home and I was called to make that happen.

Existing Trane Furnace Without Humidifier.

Existing Trane Furnace Without Humidifier.

As you can see in the picture above that there is no room below the furnace to add much of anything never mind a Honeywell TrueSTEAM humidifier. I thought about the remote mount kit from Honeywell but I would still have no room to do even that.

New Honeywell 9.0 GPD Humidifier Installed

New Honeywell 9.0 GPD Humidifier Installed

So the only solution is to raise the furnace and install a taller base can, then installing the Honeywell TrueSTEAM humidifier on to that base can. As you can see I raised the unit about 26″ and extended the gas line and shortened the return and venting. I also had to replace the existing thermostat with a Honeywell VisionIAQ, This thermostat can handle both the heating and humidity.

The reason I chose a 9.0 GPD versus a 6.0 is because of the hardwood floors that are under the rugs. I have been encountered problems using the recommended size chart that Honeywell recommends when it comes to hardwood floors.